Table 5-52
Rack with Three-phase, High-voltage 24 kVA PDU
PDU
A
A
A
A
A
A
B
B
B
B
B
B
5.3.1.8 PDU Thresholds for Oracle Exadata Database Machine X2-8 Full Rack
This section contains the PDU thresholds for Oracle Exadata Database Machine X2-8
Full Rack.
•
Table 5-53
X2-8 Full Rack with Single-phase, Low-voltage 22 kVA PDU
•
Table 5-54
X2-8 Full Rack with Three-phase, Low-voltage 24 kVA PDU
•
Table 5-55
X2-8 Full Rack with Single-phase, High-voltage 22 kVA PDU
•
Table 5-56
X2-8 Full Rack with Three-phase, High-voltage 24 kVA PDU
Table 5-53
Machine X2-8 Full Rack using a single-phase, low-voltage 22 kVA PDU.
Threshold Values for Oracle Exadata Database Machine X3-8 Full
Module/Phase
Info Low
Threshold
Module 1, phase
0
1
Module 1, phase
0
2
Module 1, phase
0
3
Module 2, phase
0
1
Module 2, phase
0
2
Module 2, phase
0
3
Module 1, phase
0
1
Module 1, phase
0
2
Module 1, phase
0
3
Module 2, phase
0
1
Module 2, phase
0
2
Module 2, phase
0
3
(page 5-48) Threshold Values for Oracle Exadata Database Machine
(page 5-48) Threshold Values for Oracle Exadata Database Machine
(page 5-48) Threshold Values for Oracle Exadata Database Machine
(page 5-49) Threshold Values for Oracle Exadata Database Machine
(page 5-48) lists the threshold values for Oracle Exadata Database
Configuring the Power Distribution Units
Pre Warning
Alarm
Threshold
Threshold
12
16
13
17
10
13
10
13
13
17
11
15
10
13
13
17
11
15
12
16
13
17
10
13
Chapter 5
5-47