Figure 4-8
4.5.3 Powering on Oracle Exadata Rack
The following procedure describes how to power on Oracle Exadata Rack:
Switch on the PDU B circuit breakers, one at a time. PDU B is on the right side of
1.
the rack when viewed from the rear. The circuit breakers are on the rear of the
Oracle Exadata Rack cabinet as shown in the following figure. Press the ON (|)
side of the toggle switch. When the breaker is in the ON position, the breakers are
flush with the side of the PDU.
Power Cord Routing Example
Note:
Oracle Exadata Database Machine X2-8 Full Rack database servers may take
up to 15 minutes to start through the normal BIOS POST tests.
Chapter 4
Powering on the System the First Time
4-13