General Environmental Requirements For Oracle Exadata Database Machine X2-8 Full Rack - Oracle EXADATA X6-2 Installation And Configuration Manual

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 1-9
Machine X2-2
Environmental
Component
Air flow front-to-back
(subject to actual data
center environment)
See Also:
"Temperature and
Humidity
Requirements
(page 1-44)", and
"Ventilation and
Cooling Requirements
(page 1-45)"
IP Addresses
See Also:
Connection and IP
Address
Requirements for
Oracle Exadata
Database Machine
(page 1-47)"
Network drops
See Also:
Connection and IP
Address
Requirements for
Oracle Exadata
Database Machine
(page 1-47)"
External connectivity
See Also:
Connection and IP
Address
Requirements for
Oracle Exadata
Database Machine
(page 1-47)"
1.1.11 General Environmental Requirements for Oracle Exadata
Database Machine X2-8 Full Rack
Table 1-10
Exadata Database Machine X2-8 Full Rack. The other sections in this chapter provide
detailed information.
(Cont.) Environmental Requirements for Oracle Exadata Database
Oracle Exadata
Database Machine
X2-2 Full Rack
Maximum:
Approximately 2,200
CFM
Typical:
Approximately 1,560
CFM
70 for Ethernet
network, assuming
"Network
single cluster
22 for InfiniBand
network
Minimum of 12
network drops
"Network
24 x 1 GbE Ethernet
ports
"Network
16 x 10 GbE Ethernet
ports (valid for M2
servers only)
At least 12 InfiniBand
ports
(page 1-19) shows the general environmental requirements for Oracle
General Environmental Requirements
Oracle Exadata
Oracle Exadata
Database Machine
Database Machine
X2-2 Half Rack
X2-2 Quarter Rack
Maximum:
Maximum:
Approximately 1,130
Approximately 550
CFM
CFM
Typical:
Typical:
Approximately 840
Approximately 410
CFM
CFM
40 for Ethernet
23 for Ethernet
network, assuming
network, assuming
single cluster (39 IP
single cluster
addresses are needed
5 for InfiniBand
for Oracle Exadata
network
Database Machine
X2-2 (with X4170 and
X4275 servers))
11 for InfiniBand
network
Minimum of 8 network
Minimum of 6 network
drops
drops
12 x 1 GbE Ethernet
6 x 1 GbE Ethernet
ports
ports
8 x 10 GbE Ethernet
4 x 10 GbE Ethernet
ports (valid for M2
ports (valid for M2
servers only)
servers only)
At least 12 InfiniBand
At least 12 InfiniBand
ports
ports
Chapter 1
1-18

Advertisement

Table of Contents
loading

Table of Contents