Oracle EXADATA X6-2 Installation And Configuration Manual page 21

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 1-4
Environmental Requirements for Oracle Exadata Database Machine
X4-8 Racks with Exadata Storage Server X5-2 Servers
Environmental Component
Weight
See Also:
"Flooring
Requirements
(page 1-34)"
Acoustic levels
Power
See Also:
"Electrical Power
Requirements
(page 1-34)"
Cooling
See Also:
"Temperature and
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
(page 1-45)"
Air flow front-to-back (subject
to actual data center
environment)
See Also:
"Temperature and
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
(page 1-45)"
IP Addresses
See Also:
"Network
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
Oracle Exadata Database
Machine X4-8 Full Rack with
Exadata Storage Server
X5-2 Servers
Extreme Flash drives:
828.1 kg (1826 lbs)
High capacity drives:
898.3 kg (1980 lbs))
86 db(A)
Extreme Flash drives
Maximum: 17.1 kVA
Typical: 12.0 kVA (varies
based on application
load)
High capacity drives
Maximum: 17.0 kVA
Typical: 11.9 kVA (varies
based on application
load)
Extreme Flash drives
Maximum: 57,300 BTU/
hour (60,452 kJ/hour)
Typical: 40,110 BTU/hour
(42,316 kJ/hour)
High capacity drives
Maximum: 56,775 BTU/
hour (59,897 kJ/hour)
Typical: 39,742 BTU/hour
(41,928 kJ/hour)
Extreme Flash drives
Maximum: Approximately
2,653 CFM
Typical: Approximately
1,857 CFM
High capacity drives
Maximum: Approximately
2,628 CFM
Typical: Approximately
1,840 CFM
44 for Ethernet network,
assuming single cluster
Up to 44 for InfiniBand
network
Chapter 1
General Environmental Requirements
Oracle Exadata Database
Machine X4-8 Half Rack
with Exadata Storage
Server X5-2 Servers
Extreme Flash drives:
526.2 kg (1160 lbs)
High capacity drives:
541.2 kg (1193 lbs)
85 db(A)
Extreme Flash drives
Maximum: 10.1 kVA
Typical: 7.1 kVA (varies
based on application
load)
High capacity drives
Maximum: 10.1 kVA
Typical: 7.0 kVA (varies
based on application
load)
Extreme Flash drives
Maximum: 33,801 BTU/
hour (35,660 kJ/hour)
Typical: 23,660 BTU/hour
(24,962 kJ/hour)
High capacity drives
Maximum: 33,688 BTU/
hour (35,541 kJ/hour)
Typical: 23,582 BTU/hour
(24,879 kJ/hour)
Extreme Flash drives
Maximum: Approximately
1,565 CFM
Typical: Approximately
1,095 CFM
High capacity drives
Maximum: Approximately
1,560 CFM
Typical: Approximately
1,092 CFM
22 for Ethernet network,
assuming single cluster
Up to 22 for InfiniBand
network
1-9