Oracle EXADATA X6-2 Installation And Configuration Manual page 233

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 5-1
(page 5-21) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Single-phase, Low-voltage PDU
Table 5-2
(page 5-21) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Three-phase, Low-voltage PDU
Table 5-3
(page 5-22) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Single-phase, High-voltage PDU
Table 5-4
(page 5-22) Threshold Values for Oracle Exadata Database Machine
X4-2 Full Rack with Three-phase, High-voltage PDU
Table 5-1
(page 5-21) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a single-phase, low-voltage PDU.
Table 5-1
Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
A
Module 1, phase
1
A
Module 1, phase
2
A
Module 1, phase
3
B
Module 1, phase
1
B
Module 1, phase
2
B
Module 1, phase
3
Table 5-2
(page 5-21) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a three-phase, low-voltage PDU.
Table 5-2
Threshold Values for Oracle Exadata Database Machine X4-2 Full
Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
A and B
Module 1, phase
1
A and B
Module 1, phase
2
A and B
Module 1, phase
3
Table 5-3
(page 5-22) lists the threshold values for Oracle Exadata Database
Machine X4-2 Full Rack using a single-phase, high-voltage PDU.
Configuring the Power Distribution Units
Info Low
Pre Warning
Threshold
Threshold
0
20
0
17
0
19
0
19
0
17
0
20
Info Low
Pre Warning
Threshold
Threshold
0
32
0
34
0
32
Chapter 5
Alarm
Threshold
24
22
24
24
22
24
Alarm
Threshold
40
42
40
5-21