Table 1-13
(Cont.) Environmental Requirements for Oracle Exadata Storage
Expansion Rack X3-2
Environmental
Oracle Exadata
Component
Storage Expansion
X3-2 Full Rack
Power
Cooling
Air flow front-to-back
(subject to actual data
center environment)
Oracle Exadata
Storage Expansion
X3-2 Half Rack
High performance
High performance
drives
drives
Maximum: 10.2
Maximum: 5.7
kVA
kVA
Typical: 7.1 kVA
Typical: 4.1 kVA
(varies based on
(varies based on
application load)
application load)
High capacity
High capacity
drives
drives
Maximum: 8.9
Maximum: 5.1
kVA
kVA
Typical: 6.2 kVA
Typical: 3.6 kVA
(varies based on
(varies based on
application load)
application load)
High performance
High performance
drives
drives
Maximum: 34,100
Maximum: 19,100
BTU/hour (36,000
BTU/hour (20,150
kJ/hour)
kJ/hour)
Typical: 23,900
Typical: 13,650
BTU/hour (25,200
BTU/hour (14,400
kJ/hour)
kJ/hour)
High capacity
High capacity
drives
drives
Maximum: 29,700
Maximum: 17,100
BTU/hour (31,300
BTU/hour (18,000
kJ/hour)
kJ/hour)
Typical: 20,800
Typical: 11,950
BTU/hour (21,950
BTU/hour (12,600
kJ/hour)
kJ/hour)
High performance
High performance
drives
drives
Maximum:
Maximum:
Approximately
Approximately
1,600 CFM
900 CFM
Typical:
Typical:
Approximately
Approximately
1,100 CFM
650 CFM
High capacity
High capacity
drives
drives
Maximum:
Maximum:
Approximately
Approximately
1,375 CFM
790 CFM
Typical:
Typical:
Approximately
Approximately
960 CFM
550 CFM
Chapter 1
General Environmental Requirements
Oracle Exadata
Storage Expansion
X3-2 Quarter Rack
High performance
drives
Maximum: 2.9
kVA
Typical: 2.0 kVA
(varies based on
application load)
High capacity
drives
Maximum: 2.6
kVA
Typical: 1.9 kVA
(varies based on
application load)
High performance
drives
Maximum: 9,500
BTU/hour (10,000
kJ/hour)
Typical: 6,700
BTU/hour (7,000
kJ/hour)
High capacity
drives
Maximum: 8,500
BTU/hour (9,000
kJ/hour)
Typical: 6,150
BTU/hour (6,500
kJ/hour)
High performance
drives
Maximum:
Approximately
440 CFM
Typical:
Approximately
310 CFM
High capacity
drives
Maximum:
Approximately
400 CFM
Typical:
Approximately
285 CFM
1-24