Oracle EXADATA X6-2 Installation And Configuration Manual page 31

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 1-10
Environmental Requirements for Oracle Exadata Database Machine
X2-8 Full Rack
Environmental Component
Weight
See Also:
"Flooring
Requirements
(page 1-34)"
Acoustic levels
Power
See Also:
"Electrical Power
Requirements
(page 1-34)"
Cooling
See Also:
"Temperature and
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
(page 1-45)"
Air flow front-to-back (subject
to actual data center
environment)
See Also:
"Temperature and
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
(page 1-45)"
IP Addresses
See Also:
"Network
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
Network drops
See Also:
"Network
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
External connectivity
See Also:
"Network
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
Oracle Exadata Database
Machine X2-8 Full Rack
(Sun Fire X4800 Oracle
Database Servers)
943.5 kg (2080 lbs)
85 db(A)
Maximum: 17.0 kW (17.4
kVA)
Typical: 11.9 kW (12.2 kVA)
(varies based on application
load)
Maximum: 58,050 BTU/hour
(61,200 kJ/hour)
Typical: 40,630 BTU/hour
(42,840 kJ/hour)
Maximum: Approximately
2,690 CFM
Typical: Approximately 1,880
CFM
45 for Ethernet network,
assuming single cluster
22 for InfiniBand network
Minimum of 5 network drops
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+
ports
12 InfiniBand ports
Chapter 1
General Environmental Requirements
Oracle Exadata Database
Machine X2-8 Full Rack
(Sun Server X2-8 Oracle
Database Servers)
980.7 kg (2162 lbs)
85 db(A)
Maximum: 17.7 kW (18.1
kVA)
Typical: 12.4 kW (112.7 kVA)
(varies based on application
load)
Maximum: 60,350 BTU/hour
(63,630 kJ/hour)
Typical: 42,280 BTU/hour
(44,580 kJ/hour)
Maximum: Approximately
2,781CFM
Typical: Approximately 1,950
CFM
45 for Ethernet network,
assuming single cluster
22 for InfiniBand network
Minimum of 5 network drops
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+
ports
12 InfiniBand ports
1-19