Table 1-16
Environmental Requirements for X6-2 Single Servers
Environmental
Exadata Storage
Component
Server X6-2 -
Extreme Flash
Weight
28.1 kg (62 lbs)
Acoustic levels
78 db(A)
Power
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Cooling
Maximum: 1,866 BTU/
hour (1,969 kJ/hour)
Typical: 1,307 BTU/
hour (1,378 kJ/hour)
Air flow front-to-back
Maximum:
(subject to actual data
Approximately 86
center environment)
CFM
Typical:
Approximately 60
CFM
Table 1-17
Environmental Requirements for X5-2 Single Servers
Environmental
Exadata Storage
Component
Server X5-2 -
Extreme Flash
Weight
28.1 kg (62 lbs)
Acoustic levels
78 db(A)
Power
Maximum: 0.6 kVA
Typical: 0.4 kVA
(varies based on
application load)
Cooling
Maximum: 2,037 BTU/
hour (2,149 kJ/hour)
Typical: 1,426 BTU/
hour (1,504 kJ/hour)
Air flow front-to-back
Maximum:
(subject to actual data
Approximately 94
center environment)
CFM
Typical:
Approximately 66
CFM
General Environmental Requirements
Exadata Storage
Database Server
Server X6-2 - High
X6-2
Capacity
33.1 kg (73 lbs)
20.4 kg (45 lbs)
78 db(A)
78 db(A)
Maximum: 0.6 kVA
Maximum: 0.665 kW
(0.678 kVA)
Typical: 0.4 kVA
(varies based on
Typical: 0.466 kW
application load)
(0.475 kVA) (varies
based on application
load)
Maximum: 2,006 BTU/
Maximum: 2,269 BTU/
hour (2,117 kJ/hour)
hour (2,394 kJ/hour)
Typical: 1,404 BTU/
Typical: 1,588 BTU/
hour (1,482 kJ/hour)
hour (1,676 kJ/hour
Maximum:
Maximum:
Approximately 93
Approximately 105
CFM
CFM
Typical:
Typical:
Approximately 65
Approximately 74
CFM
CFM
Exadata Storage
Database Server
Server X5-2 - High
X5-2
Capacity
33.1 kg (73 lbs)
20.4 kg (45 lbs)
78 db(A)
78 db(A)
Maximum: 0.6 kVA
Maximum: 0.7 kVA
Typical: 0.4 kVA
Typical: 0.5 kVA
(varies based on
(varies based on
application load)
application load)
Maximum: 2,000 BTU/
Maximum: 2,481 BTU/
hour (2,109 kJ/hour)
hour (2,617 kJ/hour)
Typical: 1,400 BTU/
Typical: 1,736 BTU/
hour (1,477 kJ/hour)
hour (1,832 kJ/hour
Maximum:
Maximum:
Approximately 93
Approximately 115
CFM
CFM
Typical:
Typical:
Approximately 65
Approximately 80
CFM
CFM
Chapter 1
1-27

Advertisement