Machine X5-8; General Environmental Requirements For Oracle Exadata Database Machine X4-2 - Oracle EXADATA X6-2 Installation And Configuration Manual

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 1-2

Machine X5-8

Environmental Component
Power
See Also:
Requirements
Cooling
See Also:
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
Air flow front-to-back (subject
to actual data center
environment)
See Also:
Humidity Requirements
(page 1-44)", and
"Ventilation and Cooling
Requirements
1.1.4 General Environmental Requirements for Oracle Exadata
Database Machine X4-2
The environmental requirements for Oracle Exadata Database Machine X4-2 depend
on the size of the system.
requirements for Oracle Exadata Database Machine X4-2. The other sections in this
chapter provide detailed information.
(Cont.) Environmental Requirements for Oracle Exadata Database
Oracle Exadata Database
Machine X5-8 Full Rack
Extreme Flash drives:
"Electrical Power
Max: 16.4 kW (16.7 kVA)
(page 1-34)"
Typical: 11.5 kW (11.7
kVA)
High capacity drives:
Max: 16.2 kW (16.6 kVA)
Typical: 11.4 kW (11.6
kVA)
Extreme Flash drives:
"Temperature and
Max: 55,935 BTU/hour
(59,012 kJ/hour)
Typical: 39,155 BTU/hour
(41,308 kJ/hour)
(page 1-45)"
High capacity drives:
Max: 55,410 BTU/hour
(58,457 kJ/hour)
Typical: 38,787 BTU/hour
(40,920 kJ/hour)
Extreme Flash drives:
Max: 2590 CFM
Typical: 1813 CFM
"Temperature and
High capacity drives:
Max: 2565 CFM
Typical: 1796 CFM
(page 1-45)"
Table 1-3
General Environmental Requirements
Oracle Exadata Database
Machine X5-8 Half Rack
Extreme Flash drives:
High capacity drives:
Extreme Flash drives:
High capacity drives:
Extreme Flash drives:
High capacity drives:
(page 1-6) shows the general environmental
Chapter 1
Max: 9.5 kW (9.7 kVA)
Typical: 6.7 kW (6.8 kVA)
Max: 9.5 kW (9.7 kVA)
Typical: 6.6 kW (6.8 kVA)
Max: 32,436 BTU/hour
(34,220 kJ/hour)
Typical: 22,705 BTU/hour
(23,954 kJ/hour)
Max: 32,323 BTU/hour
(34,101 kJ/hour)
Typical: 22,626 BTU/hour
(23,871 kJ/hour)
Max: 1502 CFM
Typical: 1051 CFM
Max: 1496 CFM
Typical: 1048 CFM
1-5