Oracle EXADATA X6-2 Installation And Configuration Manual page 52

Database machine
Hide thumbs Also See for EXADATA X6-2:
Table of Contents

Advertisement

Table 1-29
(Cont.) High-voltage 22 kVA Single Phase PDUs for Europe, the
Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and
Taiwan (2 PDUs per Rack)
Option
Frequency
Current
Power rating
Output current
Outlets
Outlet groups
Group protection (UL489 1-pole circuit
breaker)
Data center receptacle
Note:
The high-voltage 15kVA single phase PDU is no longer available. The high-
voltage 22kVA is a compatible replacement with the same receptacle and
breaker requirements
The following are needed to connect an Oracle Exadata system to a high-voltage one-
phase power source:
6 power cords for two PDUs, 25 amperes at 220/380 - 240/415 VAC 1-phase
voltage
6 receptacles to connect the PDUs to 2 IEC 60309 32A 3-pin 250VAC IP44 data
center receptacles, and requires 22 kVA, 1-phase
Figure 1-3
(page 1-37) shows the high-voltage single phase PDU power connector for
EMEA, and APAC, except for Japan and Taiwan.
Table 1-30
(page 1-40) lists the requirements for low-voltage 24 kVA three phase
PDUs. There are two PDUs per rack. The following specifications are per PDU.
Table 1-30
Low-voltage 24 kVA Three Phase PDUs for North America, South
America, Japan and Taiwan (2 PDUs per Rack)
Option
Voltage
Frequency
Current
Power rating
Output current
Electrical Power Requirements
Requirement, per PDU
50/60 Hz
32 A maximum per input
22 kVA
96 A (3 x 32 A)
42 x C13; 6 x C19
6
20A
IEC309-2P3W-IP44 32A 250VAC (Hubbell
equivalent is HBL332R6W)
Requirement, per PDU
200 - 208 VAC 3-phase
50/60 Hz
34.6 A maximum per phase
25 kVA
120 A (6 x 20 A)
Chapter 1
1-40