Table 5-50
Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Three-phase, Low-voltage 24 kVA PDU
PDU
Module/Phase
A
Module 1, phase
1
A
Module 1, phase
2
A
Module 1, phase
3
A
Module 2, phase
1
A
Module 2, phase
2
A
Module 2, phase
3
B
Module 1, phase
1
B
Module 1, phase
2
B
Module 1, phase
3
B
Module 2, phase
1
B
Module 2, phase
2
B
Module 2, phase
3
Table 5-51
(page 5-46) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a single-phase, high-voltage 22 kVA PDU.
Table 5-51
Threshold Values for Oracle Exadata Database Machine X3-8 Full
Rack with Single-phase, High-voltage 22 kVA PDU
PDU
Module/Phase
A and B
Module 1, phase
1
A and B
Module 1, phase
2
A and B
Module 1, phase
3
Table 5-52
(page 5-47) lists the threshold values for Oracle Exadata Database
Machine X3-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.
Configuring the Power Distribution Units
Info Low
Pre Warning
Threshold
Threshold
0
21
0
23
0
22
0
20
0
21
0
23
0
20
0
21
0
23
0
21
0
23
0
22
Info Low
Pre Warning
Threshold
Threshold
0
22
0
24
0
22
Chapter 5
Alarm
Threshold
27
30
28
25
27
29
25
27
29
27
30
28
Alarm
Threshold
28
30
28
5-46