Section 11
Control
11.4.6.6
402
execute command
SYNC_OK
tSynchrocheck
START_SY
SY_INPRO
tSynchronizing
IEC05000095 V1 EN-US
Figure 201:
tSynchroCheck and tSynchronizing

Interaction with switch on process bus

When the switches are modelled and controlled in a breaker IED, the information
from the switches is limited to those described in the IEC 61850 standard.
Since there is no expression for distributing the cause of failure over GOOSE, the
XLNPROXY function is used for evaluating the causes normally evaluated by the
SXCBR function.
Further, in some cases selection may also be used on the model of the switch in the
breaker IED, in case multiple controllers may access it via GOOSE. In such a case,
if the input for the stSeld data attribute in the XLNPROXY function is connected,
SCSWI automatically awaits that the switch is selected before accepting the
selection. Also, if the seSeld data attribute is set before the selection is requested,
the selection request fails.
t1
t2
en05000095.vsd
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
t2>tSynchronizing, then
blocked-by-synchrocheck in
'cause' is set
GUID-1E243260-55FC-4DA6-A314-649E0B95A2B9 v1
Technical manual