1MRK 506 382-UEN A
11.4.6.1
11.4.6.2
11.4.6.3
Line distance protection REL650 2.2 IEC
Technical manual

Functionality

The Switch controller (SCSWI) initializes and supervises all functions to properly
select and operate switching primary apparatuses. The Switch controller may
handle and operate on one multi-phase device or up to three one-phase devices.

Function block

SCSWI
BLOCK
EXE_OP
PSTO
EXE_CL
L_SEL
SEL_OP
L_OPEN
SEL_CL
L_CLOSE
SELECTED
AU_OPEN
RES_RQ
AU_CLOSE
START_SY
BL_CMD
CANC_SY
RES_GRT
POSITION
RES_EXT
OPENP OS
SY_INPRO
CLOSEPOS
SYNC_OK
POLEDISC
EN_OPEN
CMD_BLK
EN_CLOSE
L_CAUSE
XPOSL1*
POS_INTR
XPOSL2*
XOU T
XPOSL3*
IEC05000337-5-en-us.vsdx
IEC05000337 V5 EN-US
Figure 194:
SCSWI function block

Signals

Table 220:
SCSWI Input signals
Name
Type
BLOCK
BOOLEAN
PSTO
INTEGER
L_SEL
BOOLEAN
L_OPEN
BOOLEAN
L_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
BL_CMD
BOOLEAN
RES_GRT
BOOLEAN
RES_EXT
BOOLEAN
SY_INPRO
BOOLEAN
SYNC_OK
BOOLEAN
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
Table continues on next page
Default
Description
0
Block of function
2
Operator place selection
0
Select signal from local panel
0
Open signal from local panel
0
Close signal from local panel
0
Open signal from local automation function
0
Close signal from local automation function
0
Steady signal for block of the command
0
Positive acknowledge that all reservations are
made
0
Reservation is made externally
0
Synchronizing function in progress
0
Closing is permitted at set to true by the
synchrocheck
0
Enables open operation
0
Enables close operation