Monitored Data - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 7
Current protection
Name
ReclTemp
tPulse
AmbiSens
DefaultAmbTemp
DefaultTemp
Table 115:
LFPTTR Non group settings (basic)
Name
GlobalBaseSel
7.7.6
234
Values (Range)
Unit
0 - 600
Deg F
0.05 - 0.30
s
Off
-
On
-50 - 250
Deg F
-50 - 600
Deg F
Values (Range)
Unit
1 - 12
-

Monitored data

Table 116:
LCPTTR Monitored data
Name
TTRIP
TENRECL
TEMP
TEMPAMB
TERMLOAD
Table 117:
LFPTTR Monitored data
Name
TTRIP
TENRECL
TEMP
TEMPAMB
TERMLOAD
Step
Default
1
170
0.01
0.10
-
Off
1
60
1
100
Step
Default
1
1
Type
Values (Range)
INTEGER
-
REAL
-
REAL
-
REAL
-
REAL
-
Type
Values (Range)
INTEGER
-
REAL
-
REAL
-
REAL
-
REAL
-
1MRK 506 382-UEN A
Description
Temperature for reset of lockout after trip
Operate pulse length. Minimum one
execution cycle
External temperature sensor available
Ambient temperature used when
AmbiSens is set to Off.
Temperature raise above ambient
temperature at startup
Description
Selection of one of the Global Base
Value groups
PID-3908-MONITOREDDATA v7
Unit
Description
-
Estimated time to trip (in
min)
-
Estimated time to reset
of lockout (in min)
deg
Calculated temperature
of the device
deg
Ambient temperature
used in the calculations
-
Temperature relative to
operate temperature
PID-3909-MONITOREDDATA v7
Unit
Description
-
Estimated time to trip (in
min)
-
Estimated time to reset
of lockout (in min)
Temperature
Calculated temperature
Fahrenheit
of the device
Temperature
Ambient temperature
Fahrenheit
used in the calculations
-
Temperature relative to
operate temperature
Line distance protection REL650 2.2 IEC
Technical manual