Signals; Logic Diagram - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
11.3.1.4
11.3.1.5
Line distance protection REL650 2.2 IEC
Technical manual

Signals

Table 206:
SCILO Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
OPEN_EN
BOOLEAN
CLOSE_EN
BOOLEAN
Table 207:
SCILO Output signals
Name
Type
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN

Logic diagram

The function contains logic to enable the open and close commands respectively if
the interlocking conditions are fulfilled. That means also, if the switch has a
defined end position for example, open, then the appropriate enable signal (in this
case EN_OPEN) is false. The enable signals EN_OPEN and EN_CLOSE can be
true at the same time only in the intermediate and bad position state and if they are
enabled by the interlocking function. The position inputs come from the logical
nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable signals
come from the interlocking logic. The outputs are connected to the logical node
Switch controller (SCSWI). One instance per switching device is needed.
POSOPEN
POSCLOSE
OPEN_EN
CLOSE_EN
IEC04000525 V1 EN-US
Figure 189:
SCILO function logic diagram
Default
Description
0
Open position of switch device
0
Closed position of switch device
0
Open operation from interlocking logic is enabled
0
Close operation from interlocking logic is enabled
Description
Open operation at closed or interm. or bad pos. is
enabled
Close operation at open or interm. or bad pos. is
enabled
=1
1
Section 11
Control
PID-3487-INPUTSIGNALS v7
PID-3487-OUTPUTSIGNALS v7
M15086-3 v6
SCILO
EN_OPEN
&
>1
&
EN_CLOSE
&
>1
&
en04000525.vsd
379