Line distance protection REL650 2.2 IEC
Technical manual
supervised with four settable limits: low-low limit, low limit, high limit and high-
high limit. The measure value expander block (RANGE_XP) has been introduced
to enable translating the integer output signal from the measuring functions to 5
binary signals: below low-low limit, below low limit, normal, above high limit or
above high-high limit. The output signals can be used as conditions in the
configurable logic or for alarming purpose.

Function block

RANGE_XP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346-2-en.vsd
IEC05000346 V2 EN-US
Figure 315:
RANGE_XP function block
Signals
Table 434:
RANGE_XP Input signals
Name
Type
RANGE
INTEGER
Table 435:
RANGE_XP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC).
The function block converts the input integer value to five binary output signals
according to
table
436.
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high
limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
Section 14
Monitoring
SEMOD54336-4 v3
SEMOD53803-1 v2
PID-3819-INPUTSIGNALS v5
PID-3819-OUTPUTSIGNALS v5
SEMOD52462-4 v5