ABB REL650 Technical Manual page 373

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
Table 202:
BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "ready" status
Output →
READY
Input ↓
None of below
True
inputs activated
BLKON pulse
False
BLKOFF pulse
True
RESET pulse
False
INHIBIT pulse
False
SYNC
True
Table 203:
BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "in progress" status
Output →
READY
Input ↓
None of below
False
inputs activated
BLKON pulse
False
BLKOFF pulse
True
RESET pulse
False
INHIBIT pulse
False
No SYNC
False
Line distance protection REL650 2.2 IEC
Technical manual
inhibitWaitForMaster: after expiration of the tWaitForMaster time for the
WAIT input to reset, the reclosing cycle of the slave is inhibited.
longStartInhibit: if start pulse duration is longer than the tLongStartInh time,
the reclosing cycle is inhibited.
The ABORTED output indicates that the auto recloser is inhibited while it was in
one of following internal states:
inProgress: auto recloser is started and dead time is in progress.
reclaimTimeStarted: the circuit breaker closing command has started the
reclaim timer.
wait: an auto recloser, acting as slave, is waiting for a release from the master
to proceed with its own reclosing sequence.
The SYNCFAIL output indicates that the auto recloser is inhibited because the
synchrocheck or energizing check condition has not been fulfilled within the set
time interval, tSync. The ABORTED output will also be activated.
The behavior of the functionality described above is described in Table
Table
203
below.
ACTIVE
BLOCKED
False
False
False
True
False
False
False
False
False
False
False
False
ACTIVE
BLOCKED
True
False
False
True
False
False
False
False
False
False
False
False
INHIBOUT
ABORTED
False
False
False
False
False
False
False
False
True
False
False
False
INHIBOUT
ABORTED
False
False
False
False
False
False
False
False
True
True
False
True
Section 11
Control
202
and
SYNCFAIL
False
False
False
False
False
False
SYNCFAIL
False
False
False
False
False
True
367

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents