Line distance protection REL650 2.2 IEC
Technical manual
Secondary system supervision

Current circuit supervision CCSSPVC

Identification

Function description
Current circuit supervision

Functionality

Open or short circuited current transformer cores can cause unwanted operation of
many protection functions such as differential, earth-fault current and negative-
sequence current functions.
Current circuit supervision (CCSSPVC) compares the residual current from a three
phase set of current transformer cores with the neutral point current on a separate
input taken from another set of cores on the current transformer.
A detection of a difference indicates a fault in the circuit and is used as alarm or to
block protection functions expected to give inadvertent tripping.

Function block

CCSSPVC
I3P*
FAIL
IREF*
ALARM
BLOCK
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US
Figure 157:
CCSSPVC function block
Signal ISIREF must be connected in the configuration.