Function Block; Signals - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
11.4.7.2
11.4.7.3
404

Function block

SXCBR
BLOCK
XPOS
LR_SWI
EXE_OP
OPEN
EXE_CL
CLOSE
OP_BLKD
BL_OPEN
CL_BLKD
BL_CLOSE
UPD_BLKD
BL_UPD
OPENP OS
POSOP EN
CLOSEPOS
POSCLOSE
TR_POS
CBOPCAP
CNT_VAL
TR_OPEN
L_CAUSE
TR_CLOSE
EEHEALTH
RS_CNT
CBOPCAP
EEH_WARN
EEH_ALM
XIN*
IEC05000338-4-en.vsdx
IEC05000338 V5 EN-US
Figure 203:
SXCBR function block

Signals

Table 223:
SXCBR Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
CBOPCAP
INTEGER
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
EEH_WARN
BOOLEAN
EEH_ALM
BOOLEAN
XIN
GROUP
SIGNAL
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the
switch
0
Pulsed signal used to immediately close the
switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
3
Breaker operating capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ = More
0
Signal for open position of truck from I/O
0
Signal for close position of truck from I/O
0
Resets the operation counter
0
Warning from external equipment
0
Alarm from external equipment
-
Execution information from CSWI
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
M13500-3 v5
PID-6799-INPUTSIGNALS v2
Technical manual