ABB REL650 Technical Manual page 835

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
19.11
19.11.1
19.11.2
19.11.3
Table 625:
PRIMVAL Non group settings (basic)
Name
Values (Range)
Frequency
PhaseRotation
Line distance protection REL650 2.2 IEC
Technical manual
Primary system values PRIMVAL
Identification
Function description
Primary system values
Functionality
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
Settings
Unit
50.0 - 60.0
Hz
Normal=L1L2L3
-
Inverse=L3L2L1
IEC 61850
identification
PRIMVAL
Step
Default
10.0
50.0
-
Normal=L1L2L3
Section 19
Basic IED functions
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Description
Rated system frequency
System phase rotation
M15288-3 v6
PID-1626-SETTINGS v17
829