ABB REL650 Technical Manual page 547

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
Name
Values (Range)
IL3Max
IL3RepTyp
IL3AngDbRepInt
Table 381:
CMMXU Non group settings (advanced)
Name
Values (Range)
IL1ZeroDb
IL1HiHiLim
IL1HiLim
IAmpComp5
IAmpComp30
IL1LowLim
IL1LowLowLim
IAmpComp100
IAngComp5
IAngComp30
IAngComp100
IL1LimHys
IL2ZeroDb
IL2HiHiLim
IL2HiLim
IL2LowLim
IL2LowLowLim
IL2LimHys
IL3ZeroDb
IL3HiHiLim
IL3HiLim
IL3LowLim
IL3LowLowLim
IL3LimHys
Line distance protection REL650 2.2 IEC
Technical manual
Unit
0.0 - 500.0
%IB
Cyclic
-
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
1 - 100000
s
Unit
0 - 100000
m%
0.0 - 500.0
%IB
0.0 - 500.0
%IB
-10.000 - 10.000
%
-10.000 - 10.000
%
0.0 - 500.0
%IB
0.0 - 500.0
%IB
-10.000 - 10.000
%
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
-10.000 - 10.000
Deg
0.000 - 100.000
%
0 - 100000
m%
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.000 - 100.000
%
0 - 100000
m%
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.000 - 100.000
%
Step
Default
0.1
200.0
-
Cyclic
1
10
Step
Default
500
1000
0.1
150.0
0.1
120.0
0.001
0.000
0.001
0.000
0.1
80.0
0.1
60.0
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
0.001
5.000
500
1000
0.1
150.0
0.1
120.0
0.1
80.0
0.1
60.0
0.001
5.000
500
1000
0.1
150.0
0.1
120.0
0.1
80.0
0.1
60.0
0.001
5.000
Section 14
Monitoring
Description
Maximum value in % of IBase
Reporting type
Cyclic report interval (s)
Description
Magnitude zero point clamping in
0,001% of range
High High limit in % of IBase
High limit in % of IBase
Amplitude factor to calibrate current at
5% of Ir
Amplitude factor to calibrate current at
30% of Ir
Low limit in % of IBase
Low Low limit in % of IBase
Amplitude factor to calibrate current at
100% of Ir
Angle calibration for current at 5% of Ir
Angle calibration for current at 30% of Ir
Angle calibration for current at 100% of Ir
Hysteresis value in % of range, common
for all limits
Magnitude zero point clamping in
0,001% of range
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range, common
for all limits
Magnitude zero point clamping in
0,001% of range
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range, common
for all limits
541

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents