Monitoring
14.4.7.4
580
The old circuit breaker operation counter value can be used by adding the value to
the InitCBRemLife parameter. The value can be reset using the Clear menu from
LHMI or by activating the input RSTCBWR.
Accumulated energy
The Accumulated energy subfunction calculates the accumulated energy (I
on current samples, where the setting CurrExponent (y) ranges from 0.5 to 3.0. The
operation is described in figure 297.
The TRCMD output is enabled when either of the trip indications from the trip coil
circuit TRIND is high or the breaker status is OPENPOS.
I3P-IL
I3P-ILRMSPH
POSCLOSE
TRIND
LRSTIPOW
BLOCK
BLKALM
IEC12000619 V3 EN-US
Figure 297:
Functional module diagram for estimating accumulated energy
Accumulated energy calculation
Accumulated energy can be calculated either with TRIND or POSCLOSE by
selecting the AccSelCal parameter value accordingly.
The calculation is initiated with the POSCLOSE or TRIND input events. It ends
when the RMS current is lower than the AccStopCurr setting.
The ContTrCorr setting is used to determine the accumulated energy in relation to
the time the main contact opens. If the setting is positive, the calculation of energy
starts after the auxiliary contact has opened and the delay equal to the value of the
ContTrCorr setting has passed. When the setting is negative, the calculation starts
in advance by the correction time in relation to when the auxiliary contact opened.
Accumulated
energy
calculation
Alarm limit
1MRK 506 382-UEN A
GUID-0163FF0F-6E18-4CDC-87AA-578304E0872E v11
Check
IEC12000619-3-en.vsd
Line distance protection REL650 2.2 IEC
Technical manual
y
t) based
TRCMD
IPOWPH
IPOWALPH
IPOWLOPH