Technical Data - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
11.2.7
Line distance protection REL650 2.2 IEC
Technical manual
Fault
CBCLOSED
CBREADY
START
TR3P
SYNC
READY
INPROGR
1PT1
3PT1
3PT2
CLOSECB
PREP3P
UNSUCCL
IEC04000199 V3 EN-US
Figure 187:
Permanent single-phase fault, single-phase trip, two-shot
reclosing, ARMode=1ph + 1*2ph

Technical data

Table 205:
SMBRREC technical data
Function
Dead time:
shot 1 "t1 1Ph"
shot 1 "t1 2Ph"
shot 1 "t1 3Ph "
shot 1 "t1 3PhHS"
Dead time:
shot 2 "t2 3Ph"
shot 3 "t3 3Ph"
shot 4 "t4 3Ph"
shot 5 "t5 3Ph"
Extend three-phase dead time duration
"tExtended t1"
Minimum time that circuit breaker must be
closed before new sequence is allowed
"tCBClosedMin"
Wait time for the slave to close when WAIT
input has reset "tSlaveDeadTime"
Maximum allowed start pulse duration
"tLongStartInh"
Circuit breaker closing pulse duration
"tPulse"
Table continues on next page
t2 3Ph
t1 1Ph
Range or value
(0.000-120.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.100-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Section 11
Control
tReclaim
IEC04000199-3-en.vsd
M12379-1 v13
Accuracy
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
377

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents