ABB REL650 Technical Manual page 182

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 7
Current protection
I3P
U3P
AngleRCA
AngleROA
IMinOpPhSel
IEC15000266 V2 EN-US
Figure 85:
OC4 directional release block diagram
176
DFWDLx
DFWDLxx
DREVLx
Directional
Element
DREVLxx
Greater
Comparator
Different types of reset time can be selected as described in section
characteristics".
There is a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the set
operation current via a binary input ENMULTx (enable multiplier). In some
applications the operation value needs to be changed, for example due to changed
network switching state.
The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The
default values of the limits are the same as the setting limits for Ix>, and the limits
can only be used for reducing the allowed range of Ix>. This feature is used when
remote setting of the operation current value is allowed, making it possible to
ensure that the operation value used is reasonable. If Ix> is set outside Ix>Max and
Ix>Min, the closest of the limits to Ix> is used by the function. If Ix>Max is
smaller then Ix>Min, the limits are swapped. The principle of the limitation is
shown in Figure 86.
Ix>Max
Ix>
Ix>Min
IEC17000018 V1 EN-US
Figure 86:
Logic for limitation of used operation current value
Directional
Release
STLx
MAX
hi
u
MIN
lo
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
FORWARD_int
REVERSE_int
Block
x‐ means three phases 1,2 and 3
xx – means phase to phase 12,23,31
IEC15000266-2-en.vsdx
"Inverse
Ix>_used
y
IEC17000018-1-en.vsdx
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents