Function Block; Signals - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
7.4.3
7.4.4
Line distance protection REL650 2.2 IEC
Technical manual
The residual current can be calculated by summing the three-phase currents or
taking the input from the neutral CT.

Function block

EF4PTOC
I3P*
TRIP
U3P*
TRIN1
I3PPOL*
TRIN2
I3PDIR*
TRIN3
BLOCK
TRIN4
BLKTR
TRSOTF
BLKST1
START
BLKST2
STIN1
BLKST3
STIN2
BLKST4
STIN3
ENMULT1
STIN4
ENMULT2
STSOTF
ENMULT3
STFW
ENMULT4
STRV
CBPOS
2NDHARMD
CLOSECB
OPENCB
IEC06000424-5-en.vsdx
IEC06000424 V5 EN-US
Figure 90:
EF4PTOC function block

Signals

Table 86:
EF4PTOC Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
I3PPOL
GROUP
SIGNAL
I3PDIR
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKST1
BOOLEAN
BLKST2
BOOLEAN
BLKST3
BOOLEAN
BLKST4
BOOLEAN
ENMULT1
BOOLEAN
ENMULT2
BOOLEAN
ENMULT3
BOOLEAN
Table continues on next page
Default
Description
-
Group connection for operate current
-
Group connection for polarizing voltage
-
Group connection for polarizing current
-
Group connection for directional current
0
General block
0
Block of trip
0
Block of step 1 (Start and trip)
0
Block of step 2 (Start and trip)
0
Block of step 3 (Start and trip)
0
Block of step 4 (Start and trip)
0
When activated, the current multiplier is in use for
step1
0
When activated, the current multiplier is in use for
step2
0
When activated, the current multiplier is in use for
step3
Section 7
Current protection
M12619-3 v8
IP11453-1 v2
PID-6967-INPUTSIGNALS v3
183