Settings; Operation Principle - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
11.4.6.4
Table 222:
SCSWI Non group settings (basic)
Name
Values (Range)
CtlModel
PosDependent
tSelect
tResResponse
tSynchrocheck
tSynchronizing
tExecutionFB
tPoleDiscord
SuppressMidPos
InterlockChk
11.4.6.5
.
Line distance protection REL650 2.2 IEC
Technical manual
L_OPEN or L_CLOSE is operated, if the control model is Select
before operate.
If one multi-phase XCBR or two single-phase XCBR is used for a
two- or three-phase system, two or more of the inputs XPOSL1,
XPOSL2 and XPOSL3 are connected to the same source.

Settings

Unit
Dir Norm
-
SBO Enh
Always permitted
-
Not perm at 00/11
0.00 - 600.00
s
0.000 - 60.000
s
0.00 - 600.00
s
0.00 - 600.00
s
0.00 - 600.00
s
0.000 - 60.000
s
Off
-
On
Sel & Op phase
-
Op phase

Operation principle

The Switch controller (SCSWI) is provided with verification checks for the select -
execute sequence, that is, checks the conditions prior each step of the operation are
fulfilled. The involved functions for these condition verifications are interlocking,
reservation, blockings and synchrocheck.
Control handling
Two types of control models can be used. The two control models are "direct with
normal security" and "SBO (Select-Before-Operate) with enhanced security". The
Step
Default
-
SBO Enh
-
Always permitted
0.01
30.00
0.001
5.000
0.01
10.00
0.01
0.00
0.01
30.00
0.001
2.000
-
On
-
Sel & Op phase
Section 11
Description
Specifies control model type
Permission to operate depending on the
position
Maximum time between select and
execute signals
Allowed time from reservation request to
reservation granted
Allowed time for synchrocheck to fulfil
close conditions
Supervision time to get the signal
synchronizing in progress
Maximum time from command execution
to termination
Allowed time to have discrepancy
between the poles
Mid-position is suppressed during time
tIntermediate; tIntermediate is set on
each connected XCBR/XSWI function
individually
Selection if interlock check should be
done in select phase
Control
PID-6798-SETTINGS v3