Operation Principle - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
17.4.10.6
Line distance protection REL650 2.2 IEC
Technical manual

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and
communication error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the binary single
point values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
Station communication
Data Value
Data Valid
Updated
1
0
0
0
0
0
0
0
0
0
0
0
0
Updated
1
Updated
1
0
0
Section 17
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0
687