Technical Data - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
14.10.8
14.11
14.11.1
14.11.2
Line distance protection REL650 2.2 IEC
Technical manual

Technical data

Table 448:
L4UFCNT technical data
Function
Counter value
Max. count up speed
Running hour-meter TEILGAPC
Identification
Function Description
Running hour-meter
Functionality
The Running hour-meter (TEILGAPC) function is a function that accumulates the
elapsed time when a given binary signal has been high, see also figure 322.
BLOCK
RESET
IN
ADDTIME
tAddToTime
99 999.9 h
tWarning
tAlarm
-1
q
= unit delay
IEC15000321 V1 EN-US
Figure 322:
TEILGAPC logics
The main features of TEILGAPC are:
Applicable to very long time accumulation (≤ 99999.9 hours)
Supervision of limit transgression conditions and rollover/overflow
Possibility to define a warning and alarm with the resolution of 0.1 hours
Retain any saved accumulation value at a restart
Range or value
0-65535
30 pulses/s (50% duty cycle)
IEC 61850
IEC 60617
identification
identification
TEILGAPC
-
Time Accumulation
with Retain
-1
q
a
a>b
b
a
a>b
b
a
a>b
b
Section 14
Monitoring
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Accuracy
-
-
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
ANSI/IEEE C37.2 device
number
-
GUID-464FB24F-B367-446C-963A-A14841943B87 v2
ACC_HOUR
ACC_DAY
OVERFLOW
&
WARNING
&
ALARM
&
IEC15000321-1-en.vsd