Section 11
Control
396
parameter CtlModel defines which one of the two control models is used. The
control model "direct with normal security" does not require a select whereas, the
"SBO with enhanced security" command model requires a select before execution.
The command sequence for a command with control mode SBO with enhanced
security is shown in figure 195, with control mode direct with normal security is
shown in figure 196.
Client
IEC16000083 V1 EN-US
Figure 195:
Example of command sequence for a successful close command
when the control model SBO with enhanced security is used
Reservation
logic
select
SEL_CL = TRUE
RES_RQ = TRUE
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0
requestedPosition = 10
opRcvd = TRUE
opOK = TRUE, tOpOk
operateAck/AddCause = 0
POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE
RES_RQ = FALSE
RES_GRT = FALSE
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
SCSWI
SXCBR
EXE_CL
operateAck/AddCause = 0
POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0
IEC16000083=1=en=Original.vsdx
Technical manual