Inverse Characteristics - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
23.3
Line distance protection REL650 2.2 IEC
Technical manual

Inverse characteristics

Table 674:
ANSI Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
× +
t
B k tDef
(
)
ç
÷
P
ç
-
÷
I
1
è
ø
EQUATION1249-SMALL V2 EN-US
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN-US
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
Inverse time characteristics
Range or value
0.10 ≤ k ≤ 3.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0 ,
tr=29.1
A=19.61, B=0.491, P=2.0 ,
tr=21.6
A=0.0086, B=0.0185, P=0.02,
tr=0.46
A=0.0515, B=0.1140, P=0.02,
tr=4.85
A=64.07, B=0.250, P=2.0,
tr=30
A=28.55, B=0.712, P=2.0,
tr=13.46
A=0.086, B=0.185, P=0.02,
tr=4.6
Section 23
IP15797-1 v2
M12388-1 v21
Accuracy
ANSI/IEEE C37.112 ,
±2.0% or ±40 ms
whichever is greater
897

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents