Section 13
Logic
13.5.5
Table 292:
WRNCALH Group settings (basic)
Name
Operation
13.5.6
488
Name
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
Table 291:
WRNCALH Output signals
Name
WARNING

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The logic for group warning WRNCALH block is provided with 16 input signals
and 1 WARNING output signal. The function block incorporates internal logic OR
gate in order to provide grouping of connected input signals to the output
WARNING signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
INPUT1
³1
INPUT16
IEC13000192 V1 EN-US
Type
Default
Description
BOOLEAN
0
Binary input 9
BOOLEAN
0
Binary input 10
BOOLEAN
0
Binary input 11
BOOLEAN
0
Binary input 12
BOOLEAN
0
Binary input 13
BOOLEAN
0
Binary input 14
BOOLEAN
0
Binary input 15
BOOLEAN
0
Binary input 16
Type
Description
BOOLEAN
OR function betweeen inputs 1 to 16
Step
Default
-
Off
1MRK 506 382-UEN A
PID-4127-OUTPUTSIGNALS v3
Description
Operation Off / On
GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2
200 ms
t
IEC13000192-1-en.vsd
Line distance protection REL650 2.2 IEC
Technical manual
PID-4127-SETTINGS v3