Section 17
Station communication
17.8
17.8.1
17.8.2
17.8.2.1
17.8.2.2
738
IEC 60870-5-103 communication protocol
Introduction
IEC 60870-5-103 communication protocol is mainly used when a protection IED
communicates with a third party control or monitoring system. This system must
have software that can interpret the IEC 60870-5-103 communication messages.
Measurands for IEC 60870-5-103 I103MEAS
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The set of connected input will control which ASDUs (Application Service Data
Units) are generated.
9 Will be generated if at least IL1 is connected. IL2, IL3, UL1, UL2, UL3, P,
Q, F are optional but there can be no holes.
3.4 Will be generated if IN and UN are present.
3.3 Will be generated if IL2, Ul1L2, P and Q present.
3.2 Will be generated if IL2, UL1L2 and P or Q missing.
3.1 Will be generated if IL2 present and IL1 missing (otherwise IL2 in 9).
Description for I103MEAS function block:
9 = IL1
3.4 = IN AND UN
3.3 = IL2 AND UL1L2 AND P AND Q
3.2 = IL2 AND UL1L2 AND NOT 3.3
3.1 = IL2 AND NOT (3.2 OR 3.3 OR 9)
Identification
Function description
Measurands for IEC 60870-5-103
Function block
IEC 60617
name
identification
I103MEAS
-
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
IP14615-1 v2
M11910-3 v3
GUID-557FB587-9127-4D99-B2C6-16445E06F220 v3
GUID-3E1AB624-1B68-4018-B1BA-BC2C811F8F74 v1
ANSI/IEEE C37.2
device number
-
Technical manual