Section 17
Station communication
17.8.6
17.8.6.1
17.8.6.2
744
Function status fault protection for IEC 60870-5-103
I103FLTPROT
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that
is triggering the Disturbance Recorder and the respective configured signal to the
IEC 60870-5-103 I103FLTPROT.
Identification
Function description
Function status fault protection for IEC
60870-5-103
Function block
IEC 60617
name
identification
I103FLTPROT
-
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1
GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1
ANSI/IEEE C37.2
device number
-
Technical manual