1MRK 506 382-UEN A
Line distance protection REL650 2.2 IEC
Technical manual
Y
High-high limit
High limit
X_RANGE=0
Low limit
X_RANGE=2
Low-low limit
X_RANGE=4
IEC05000657 V3 EN-US
Figure 49:
Presentation of operating limits
Each analogue output has one corresponding supervision level output
(X_RANGE). The output signal is an integer in the interval 0-4 (0: Normal, 1:
High limit exceeded, 3: High-high limit exceeded, 2: below Low limit and 4: below
Low-low limit).
The logical value of the functional output signals changes according to figure 49.
The user can set the hysteresis (XLimHyst), which determines the difference
between the operating and reset value at each operating point, in wide range for
each measuring channel separately. The hysteresis is common for all operating
values within one channel.
Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The
measurement is continuous for each measured quantity separately, but the reporting
of the value to the higher levels depends on the selected reporting mode. The
following basic reporting modes are available:
Cyclic reporting (Cyclic)
Amplitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)
Amplitude Deadband and 5s cyclic
Amplitude Deadband and 30s cyclic
Amplitude Deadband and 1min cyclic
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting
(XRepTyp). The measuring channel reports the value independent of amplitude or
integral dead-band reporting.
Y = Magnitude of the Measured Quantity
X_RANGE = 3
X_RANGE= 1
Hysteresis
X_RANGE=0
Section 6
Impedance protection
IEC05000657-3-en.vsdx
SEMOD54417-150 v4
SEMOD54417-158 v3
t
117