ABB REL650 Technical Manual page 407

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
Line distance protection REL650 2.2 IEC
Technical manual
execute command
position L1
open
close
position L2
open
close
position L3
open
close
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position
open
close
tExecutionFB timer
* The cmd termination will be delayed one execution sample .
IEC05000094 V2 EN-US
Figure 200:
tExecutionFB
The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
The parameter tSynchronizing is used to define the maximum allowed time
between the start signal for synchronizing and the confirmation that synchronizing
is in progress.
Section 11
*
t1
APCtExecutionFB=IEC0
5000094=2=en=Original
.vsd
Control
t1>tExecutionFB, then
long-operation-time in
'cause' is set
401

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents