1MRK 504 152-UEN B
Off
SPA
LON
DNP
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called BININPUT. For a
description of the BININPUT settings, see the
The system time can be set manually, either via the local HMI or via any of the communication
ports. The time synchronization fine tunes the clock (seconds and milliseconds).
The parameter
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
Off
SNTP -Server
22.13.2.3

Process bus IEC 61850-9-2LE synchronization

When process bus communication (IEC 61850-9-2LE protocol) is used, it is essential that the
merging units are using the same time source as the IED. To achieve this, a satellite-controlled
clock shall provide time synchronization to the IED (either internal GPS or via IRIG-B 00x with
IEEE1344 support) and to the merging units (via for instance PPS). For the time
synchronization of the process bus communication, GPS Time Module (GTM) and/or IRIG-B
module can be used. If the IED contains a GTM, the merging unit can be synchronized from the
PPS output of the GTM.
Application manual
SyncMaster defines if the IED is a master, or not a master for time
Set the course time synchronizing source (
time synchronization of line differential function is used. Set the fine time
synchronization source (
complete time synchronization. GPS alone shall synchronize the analogue
values in such systems.
All protection functions will be blocked if the AppSynch parameter is set to
Synch while there is no 9-2 synchronization source. For more information
please refer to the "IEC/UCA 61850-9-2LE communication protocol" section.
Technical Manual .
SyncMaster can have the following values:
CoarseSyncSrc ) to Off when GPS
FineSyncSource ) to GPS . The GPS will thus provide the
Section 22
Basic IED functions
GUID-6E384BDB-5598-4108-99B4-0B4A4E1828B2 v3