ABB REL650 Technical Manual page 484

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 13
Logic
478
STARTCOMB
To make it possible to provide the directional information from a protection
function, a STARTCOMB block is used in between the application function and the
Start Matrix function.
The STARTCOMB function has one block input and 14 Boolean inputs that
convert the 14 Boolean inputs into a WORD output STDIR, see Figure 249.
STDIRX =[ b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14 ]
b0=
START (start)
b1=
FW (forward)
b2=
REV (reverse)
b3=
STL1 (startL1)
b4=
FWL1 (forwardL1)
b5=
REVL1 (reverseL1)
b6=
STL2 (startL2)
b7=
FWL2 (forwardL2)
b8=
REVL2 (reverseL2)
b9=
STL3 (startL3)
b10=
FWL3 (forwardL3)
b11=
REVL3 (reverseL3)
b12=
STN (startN)
b13=
FWN (forwardN)
b14=
REVN (reverseN)
STARTCOMB
BLOCK
STDI R
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US
Figure 249:
STARTCOMB
Protection functions
Some protection functions are provided with start and directional outputs, for
example:
1MRK 506 382-UEN A
Line distance protection REL650 2.2 IEC
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents