Unblocking Scheme - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 12
Scheme communication
12.4.6.3
454
In the overreaching alternative, an overreaching directional residual overcurrent
measurement element will be used as sending criterion of the permissive input
signal CSOR. Also the underreaching input signal CSUR can initiate sending.
BLOCK
CR
CACC
BLKCS
Overreach
AND
CSOR
CSUR
IEC05000280 V4 EN-US

Unblocking scheme

In unblocking scheme, the lower dependability in permissive scheme is overcome
by using the loss of guard signal from the communication equipment to locally
create a receive signal. It is common or suitable to use the function when older, less
reliable, power line carrier (PLC) communication is used.
The unblocking function uses a guard signal CRG, which must always be present,
even when no CR signal is received. The absence of the CRG signal for a time
longer than the setting tSecurity time is used as a CR signal, see figure 233. This
also enables a permissive scheme to operate when the line fault blocks the signal
transmission.
The received signal created by the unblocking function is reset 150 ms after the
security timer has elapsed. When that occurs an output signal LCG is activated for
signaling purpose. The unblocking function is reset 200 ms after that the guard
signal is present again.
AND
0 - 60 s
AND
AND
t
tCoord
AND
AND
25 ms
OR
t
1MRK 506 382-UEN A
CRL
25 ms
TRIP
t
50 ms
t
CS
OR
IEC05000280.vsd
Line distance protection REL650 2.2 IEC
Technical manual