ABB REL650 Technical Manual page 390

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

Section 11
Control
384
Cause
Name
number
-25
Blocked-for-close-
cmd
-30
Long-operation-time
-31
Switch-not-start-
moving
-32
Persistent-
intermediate-state
-33
Switch-returned-to-
init-pos
-34
Switch-in-bad-state
-35
Not-expected-final-
position
Table 209:
Translation of cause values for IEC 61850 edition 2 and edition 1
Internal Cause
AddCause in IEC 61850-8-1
Number
Ed 2
0
25
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
24
24
26
26
27
27
Table continues on next page
Description
Blocked for Close Command
Operation time too long
Switch did not start moving
Switch stopped in intermediate state
Switch returned to the initial position
Switch is in a bad position state
Switch did not reach the expected final position
Ed 1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
16
17
18
3
3
-23
6
12
Line distance protection REL650 2.2 IEC
1MRK 506 382-UEN A
Supported
Name
None
Not-supported
Blocked-by-switching-hierarchy
Select-failed
Invalid-position
Position-reached
Parameter-change-in-execution
Step-limit
Blocked-by-Mode
Blocked-by-process
Blocked-by-interlocking
Blocked-by-synchrocheck
Command-already-in-execution
Blocked-by-health
1-of-n-control
Abortion-by-cancel
Time-limit-over
Abortion-by-trip
Object-not-selected
Object-already-selected
No-access-authority
Blocked-by-command
Inconsistent-parameters
Locked-by-other-client
Technical manual
X
X
X
X
X
X
X