Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
17.8.8.5
Table 538:
I103SUPERV Non group settings (basic)
Name
Values (Range)
FunctionType
17.8.9
17.8.9.1
17.8.9.2
Line distance protection REL650 2.2 IEC
Technical manual
Name
37_IBKUP
38_VTFF
46_GRWA
47_GRAL

Settings

Unit
1 - 255
-
Status for user defined signals for IEC 60870-5-103
I103USRDEF
Functionality
I103USRDEF is a function block with user defined input signals in monitor
direction. Each instance is associated with a Function Type (FUN) and each input
signal with an Information Number (INF). Additionally, all input signals may be
defined to use relative time and how to respond to a GI request.
The user is responsible for assigning a proper FUN value and proper INF values to
all connected inputs. See Settings for details.
Identification
Function description
Status for user defined signals for IEC
60870-5-103
Type
Default
Description
BOOLEAN
0
Information number 37, I high-high back-up
protection
BOOLEAN
0
Information number 38, fuse failure VT
BOOLEAN
0
Information number 46, group warning
BOOLEAN
0
Information number 47, group alarm
Step
Default
1
1
Function block
name
I103USRDEF
Section 17
Station communication
Description
Function type (1-255)
GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3
GUID-474FDF39-CEFC-4370-9393-13BE62159969 v2
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
PID-3976-SETTINGS v5
749