Technical Data - ABB REL650 Technical Manual

Hide thumbs Also See for REL650:
Table of Contents

Advertisement

1MRK 506 382-UEN A
20.2.8.6
Line distance protection REL650 2.2 IEC
Technical manual
Name
Type
BO23
BOOLEAN
BO24VALUE
BOOLEAN
BO24FORCE
BOOLEAN
BO24
BOOLEAN

Technical data

Table 644:
BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Binary outputs
Max system voltage
Test voltage across open contact, 1 min
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
Making capacity at inductive load with L/R > 10 ms
0.2 s
1.0 s
Breaking capacity for AC, cos j > 0.4
Breaking capacity for DC with L/R < 40 ms
Maximum 72 outputs may be activated simultaneously with
influencing factors within nominal range. After 6 ms an additional
24 outputs may be activated. The activation time for the 96 outputs
must not exceed 200 ms. 48 outputs can be activated during 1 s.
Continued activation is possible with respect to current
consumption but after 5 minutes the temperature rise will adversely
affect the hardware life. Maximum two relays per BOM/IOM
should be activated continuously due to power dissipation.
Values (Range)
Unit
0=Normal
-
1=Forced
2=Blocked
1=1
-
0=0
0=Normal
-
1=Forced
0=Normal
-
1=Forced
2=Blocked
Trip and Signal relays
24
250 V AC, DC
1000 V rms
8 A
10 A
12 A
30 A
10 A
250 V/8.0 A
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Section 20
IED hardware
Description
Binary output 23 status
Binary output 24 value
nary output 24 force
Binary output 24 status
SEMOD55355-1 v1
M12441-1 v8
853

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents