Section 17 Technical Data - ABB REB650 Technical Manual

Relion 650 series busbar protection
Hide thumbs Also See for REB650:
Table of Contents

Advertisement

1MRK 505 277-UUS C
Section 17
17.1
17.2
Technical Manual
Technical data
Dimensions
Table 381:
Dimensions of the IED - 3U full 19" rack
Description
Width
Height
Depth
Weight box
Weight LHMI
Power supply
Table 382:
Power supply
Description
V
n
V
variation
n
Maximum load of auxiliary voltage
supply
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
Value
17.40 inches (442 mm)
5.20 inches (132 mm), 3U
9.82 inches (249.5 mm)
<22.04 lbs (10 kg)
2.87 lbs (1.3 kg)
600PSM02
48, 60, 110, 125 V DC
80...120% of V
(38.4...150 V
n
DC)
35 W for DC
40 W for AC
Max 15% of the DC value (at frequency of 100 and 120 Hz)
50 ms at V
n
Section 17
Technical data
600PSM03
100, 110, 120, 220, 240 V AC,
50 and 60 Hz
110, 125, 220, 250 V DC
85...110% of V
(85...264 V AC)
n
80...120% of V
(88...300 V DC)
n
449

Hide quick links:

Advertisement

Table of Contents
loading