Functional Diagrams For Control And Interlocking - ABB RELION 615 Series Applications Manual

Generator and interconnection protection
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Section 3
REG615 standard configurations
3.3.3.4
56
It is assumed that there is no external resistor in the circuit-breaker
tripping coil circuit connected in parallel with the circuit breaker
normally open auxiliary contact.
Set the parameters for TCSSCBR1 properly.
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_ALARM
TCSSCBR2_ALARM
GUID-C01BBF87-22FF-437E-9A40-23CCEA199C51 V2 EN
Figure 43:
Trip circuit supervision function
TRPPTRC1_TRIP
TRPPTRC2_TRIP
X110_BI8_CB_OPENED
GUID-77EE438D-ABB9-41D2-84F4-930507384B0F V2 EN
Figure 44:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The main purpose of the synchronism and energizing check SECRSYN is to provide
control over the closing of the circuit breakers in power networks to prevent the
closing if conditions for synchronism are not detected. The energizing function allows
closing, for example, when one side of the breaker is dead.
SECRSYN measures the bus and line voltages and compares them to set the
conditions. When all the measured quantities are within set limits, the output
SYNC_OK is activated for allowing closing or closing the circuit breaker. The
SECRSYN1_SYNC_OK output signal of SECRSYN is connected to SYNC_OK input
of CBXCBR through control logic. The function is blocked in case of terminal side or
bus side MCB is open.
TCSSCBR1(TCS(1)
BLOCK
ALARM
TCSSCBR2(TCS(2)
BLOCK
ALARM
OR
B1
O
B2
OR6
B1
O
B2
B3
B4
B5
B6
1MRS758272 B
TCSSCBR1_ALARM
TCSSCBR2_ALARM
TCSSCBR_ALARM
TCSSCBR_BLOCKING
REG615