Functional Diagrams For Control And Interlocking - ABB RELION 615 Series Applications Manual

Feeder protection and control relay
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

1MAC109016-MB C
3.3.3.4
REF615 ANSI
Application Manual
TCSSCBR_BLOCKING
TCSSCBR_BLOCKING
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-1_ALARM
GUID-09D826A2-9C1F-45E2-8382-FFC58B98DAE7 V1 EN
Figure 32:
Trip circuit supervision function
TRPPTRC1_86/94-1_TRIP
TRPPTRC2_86/94-2_TRIP
X120_BI3_CB_OPEN
GUID-A0E5F33A-B395-4EE7-92A9-C1222EF942BD V1 EN
Figure 33:
Logic for blocking of trip circuit supervision

Functional diagrams for control and interlocking

The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
can be activated using the configuration logic, which is based on the status of the trip
logics. However, other signals can be connected based on the application needs.
The SYNC_ITL_BYP input can be used, for example, to always enable the closing of the
circuit breaker when the circuit breaker truck is in the test position. SYNC_ITL_BYP
overrides, for example, active interlocking conditions when the circuit breaker truck is
closed in service position.
REF615 standard configurations
TCSSCBR1
BLOCK
ALARM
O:74|T:5|I:1
TCSSCBR2
BLOCK
ALARM
O:75|T:5|I:2
OR
B1
O
B2
O:76|T:2.5|I:13
OR6
B1
O
B2
B3
B4
B5
B6
O:73|T:2.5|I:19
Section 3
TCSSCBR1_TCM-1_ALARM
TCSSCBR2_TCM-1_ALARM
TCSSCBR_ALARM
TCSSCBR_BLOCKING
59