Functional Diagrams For Control And Interlocking - ABB RELION 611 Series Applications Manual

Busbar and multipurpose differential protection and control
Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757455 E
3.4.3.3
REB611
Application Manual

Functional diagrams for control and interlocking

OSWGAPC1
IN_1
HIAPDIF1_OPERATE
IN_2
HIBPDIF1_OPERATE
IN_3
HICPDIF1_OPERATE
IN_4
EHLPTOC1_OPERATE
IN_5
EFHPTOC1_OPETATE
SELGAPC1_External Trip
IN1
GOOSERCV_BIN 2_OUT
IN2
OR
GOOSERCV_BIN 3_OUT
SELGAPC1_RST_LKOUT
CBXCBR1_EXE_OP
OSWGAPC2
IN_1
HIAPDIF1_OPERATE
IN_2
HIBPDIF1_OPERATE
IN_3
HICPDIF1_OPERATE
IN_4
EHLPTOC1_OPERATE
IN_5
EFHPTOC1_OPETATE
IN_6
CCBRBRF1_TRRET
SELGAPC1_External Trip
IN1
IN2
GOOSERCV_BIN 2_OUT
OR
GOOSERCV_BIN 3_OUT
SELGAPC1_RST_LKOUT
GUID-AFCBCEC5-678B-4F8B-9963-FFE91A7F1233 V3 EN
Figure 22:
Master trip
The operate signals from the protections and an external trip are connected to the two
trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding
master trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit
breaker from local or remote CBXCBR1_EXE_OP or from the autoreclosing
DARREC1_OPEN_CB are connected directly to the output contact PO3
(X100:15-19).
TRPPTRC1 and TRPPTRC2 provide the lockout/latching function, event generation
and the trip signal duration setting. One binary input through SELGAPC1 can be
connected to the RST_LKOUT input of master trip. If the lockout operation mode is
selected, it is used to enable external reset.
REB611 standardized configuration
MASTER TRIP #1
TRPPTRC1
OUT
OR
BLOCK
OR
OPERATE
RST_LKOUT
MVGAPC1
Q1
Q2
MASTER TRIP #2
TRPPTRC2
OUT
OR
BLOCK
OR
OPERATE
RST_LKOUT
MVGAPC1
Q1
Q2
Section 3
SELGAPC3
TRIP
IN_1
OUT_5
OR
CL_LKOUT
SELGAPC3
IN_2
OUT_6
TRIP
CL_LKOUT
X100 PO3
X100 PO4
39