How To Change Settings - ABB REU 610 Operator's Manual

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
4.2.2.2.
30
Voltage Relay
Operator's Manual - ANSI Version
The views are used for reading and setting parameters, which are divided into
two main groups:
SETTINGS
*
CONFIGURATION
*

How to change settings

The actual settings consist of the settings of group 1 or group 2, depending on
which group has been selected to be active (indicated by an asterisk "*"). The
actual settings can be seen in the first parameter menu, for example:
SETTINGS\PROTEC. ELEMENTS\59P-1 VTx0.00
Submenu
PROTEC. ELEMENTS
59P-1
VTx0.00
Fig. 4.2.2.2.-1
Setting parameters in setting group 1 and setting group 2
By switching between setting groups 1 and 2, you can activate a whole group
of settings at the same time. Switch between the setting groups as follows:
With the parameter GROUP 1/GROUP 2 under the main menu group
*
SETTINGS.
With a digital input signal, provided that SGB1...5/4 has been set to 1 in
*
both setting groups (GRP1 and GRP2).
With parameter V150 via the SPA bus.
*
When a large number of settings is to be altered, for example
during the commissioning of the relay systems, use a PC
equipped with the necessary software.
If no PC is available, or when only a few settings are to be altered:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select the main menu group SETTINGS and the
wanted group menu (for example PROTEC. ELEMENTS), and press
3. Use
or
to select the parameter to be changed and press
to select setting group 1 or 2 (GRP1 or GRP2). The active
4. Use
or
setting group is indicated by an asterisk "*".
5. Enter the setting mode by pressing
If the default password 999 is still valid, no password is required.
Parameter Menu
SETTINGS
* GRP 1
:0.00
GRP 2
:0.00
and give the password if required.
1MRS755971
Confirm
Cancel
A051578
.
.