Connecting Local Hmi To A Relay Through Station Network - ABB RELION REX640 Operation Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759118 A
7.4.3.2
REX640
Operation Manual

Connecting local HMI to a relay through station network

PCM600 or WHMI can be used to read the network settings of the relay's station port
via Configuration/Communication/Ethernet/Network address.
1.
On the LHMI, tap Network Settings to configure the network settings of the
main unit port.
Network settings are also available as an Advanced page.
GUID-EFDCCB00-4FDF-4F2A-A28D-F03F2EC37450 V1 EN
Figure 91:
Opening the Network Settings page
2.
On the Network Settings page, clear the Automatic Address check box and
edit the network settings of the LHMI main unit port.
These settings should match the settings in Configuration/Communication/
Ethernet/Network address.
Enter the IP address for the LHMI's main unit port, not the
relay's station port. If a router is used between the relay and the
LHMI, check the correct gateway IP address.
Section 7
Commissioning
111