Section 5
Connecting
5.2.1
5.3
36
See the application manual for product-specific connection diagrams.
Connecting ring-lug type wires
Ring-lug type insulated terminal can be used for signal connector X120. The
maximum outside diameter for the M4 ring-lug type terminals is 9 mm.
Connecting protective earthing
The earth lead must be at least 6.0 mm
cross section of the wire must be increased.
Use fine copper wire as the earth lead.
1.
Loosen the protective earth screw (T20) to connect a separate earth protection
lead.
1MRS757452 D
2
. If the earth lead is long, the
611 series
Installation Manual