1MRK 505 264-UEN A
Section 7
7.1
Testing disturbance report
7.1.1
Introduction
The following sub-functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Trip value recorder
•
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is not
possible to only switch these sub-functions off. The disturbance report function is switched
off (parameter
Settings/Monitoring/Disturbance report/1:DRPRDRE.
7.1.2
Disturbance report settings
When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test mode
is switched off all recordings made during the test session are cleared.
Setting
on the local HMI under Main menu/Settings/IED Settings/Monitoring/Disturbance report/
1:DRPRDRE.
7.2
Identifying the function to test in the technical
reference manual
Use the technical manual to identify function blocks, logic diagrams, input and output signals,
setting parameters and technical data.
7.3
Testing differential protection functions
7.3.1
High impedance differential protection HZPDIF
Prepare the IED for verification of settings as outlined in the section
verify
settings".
Values of the logical signals for HZPDIF are available on the local HMI under Main menu/Tests/
Function status/Differential/HZPDIF(87,IdN)/X:HZPDIF. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.
7.3.1.1
Verifying the settings
Busbar protection REB650
Commissioning manual
Testing functionality
Operation = Off ) in PCM600 or the local HMI under Main menu/Settings/IED
OpModeTest for the control of the disturbance recorder during test mode are located
© Copyright 2011 ABB. All rights reserved
Section 7
Testing functionality
M17101-2 v3
M11746-2 v4
M11748-2 v3
SEMOD55257-42 v3.2.1
"Preparing the IED to
SEMOD55257-46 v2