Field Supply; Connection; Figure 16: Field Supply For Fieldbus Couplers/Controllers (Example); Table 15: Legend For Figure "Field Supply For Fieldbus Couplers/Controllers - WAGO 750-626/040-000 Manual

Design notes /xtr guidelines and recommendations for increasing operational safety
Hide thumbs Also See for 750-626/040-000:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-xxxx/0040-xxxx Design Notes /XTR
Pos : 34.22 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung - Übersc hrift 3 @ 3\mod_1232950080953_21.doc x @ 26688 @ 3 @ 1
6.5.3

Field Supply

Pos : 34.23 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung - Ansc hluss @ 3\mod_1232950082031_21.doc x @ 26696 @ 4 @ 1
6.5.3.1

Connection

Sensors and actuators can be directly connected to the relevant channel of the I/O
module in 1, 2, 3 or 4 conductor connection technology. The I/O module supplies
power to the sensors and actuators. The input and output drivers of some I/O
modules require the field side supply voltage.
Pos : 34.24 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung - Ansc hluss - Ei ns peis ung felds eitig (Standard + erweiterter EC O) @ 3\mod_1232950087703_21.doc x @ 26712 @ @ 1
The fieldbus coupler/controller provides field side power (DC 24 V). In this case
it is a passive power supply without protection equipment.
Pos : 34.25 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung - Ansc hluss - Potentialgruppen mit Ei ns peis eklemme XTR @ 17\mod_1382697121058_21.doc x @ 135120 @ @ 1
Power supply modules with or without diagnostic capability are available for the
power supply of other field potentials (e.g. 24 VDC, 0 VAC/DC ... 230 VAC/DC,
120 VAC, 230 VAC). The power supply modules can also be used to set up
various potential groups. The connections are connected in pairs to a power
contact.
Pos : 34.26 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung XTR - Ansc hluss - Bil d: Fel dversorgung (Standar d + erweiterter EC O) @ 16\mod_1373895183197_21.doc x @ 126188 @ @ 1

Figure 16: Field Supply for Fieldbus Couplers/Controllers (Example)

Table 15: Legend for Figure "Field Supply for Fieldbus Couplers/Controllers"

Position Description
1
2
3
Pos : 34.27 /Serie 750 ( WAGO-I/O-SYST EM)/Systembesc hrei bung/Vers orgung/F eldvers orgung - Ansc hluss -Weiterleitung Versorgungss pg., Strombelas tung 10 A, neue Ei nspeis eklemme @ 8\mod_1279805441785_21.doc x @ 60845 @ @ 1
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual basis.
Manual
Version 1.2.0
Field supply 24 VDC
Field supply 0 V
Power jumper contacts (potential distribution to adjacent I/O modules)
Connect Devices
41